Check The Additional Amount Of Refrigerant; Additional Amount Of Refrigerant By Pipe Length - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

• Check the additional amount of refrigerant.

Checklist 2
Calculate the additional amount of refrigerant from the additional amount of refrigerant (A) by the pipe diameter on
the liquid side, the pipe length to be connected, and the corrective amount of refrigerant (C) according to system
horsepower.
Additional amount
of refrigerant
First, enter the total length for each liquid pipe diameter in the following table, and then calculate the additional
amount of refrigerant by pipe length.
<Additional amount of refrigerant by pipe length>
Pipe diameter on the liquid
side
Ø6.4
Ø9.5
Ø12.7
Ø15.9
Ø19.0
Ø22.2
Next, refer to the following table for the corrective amount of refrigerant (C) according to system horsepower.
<Corrective amount of refrigerant according to system horsepower>
Standard type
High Efficiency type
Lastly, add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by
combined horsepower (C). This is the final additional amount of refrigerant.
If a minus sign is indicated as the result, do not add the refrigerant (= 0 kg).
<Additional amount of refrigerant>
Additional amount of refrigerant by pipe length (A)
Corrective amount of refrigerant according to combined horsepower (C)
Additional amount of refrigerant
Downloaded from
www.Manualslib.com
Actual liquid pipe length × Additional amount
=
of refrigerant per 1 m of liquid pipe
Standard amount of
refrigerant
kg/m
0.025 ×
0.055 ×
0.105 ×
0.160 ×
0.250 ×
0.350 ×
Additional amount of refrigerant by pipe length (A)
Combined HP (HP)
8
8HP
10
10HP
12
12HP
14
14HP
16
16HP
18
10HP
20
10HP
22
12HP
24
12HP
26
16HP
28
16HP
30
16HP
32
16HP
34
12HP
36
12HP
38
16HP
40
16HP
42
16HP
44
16HP
46
16HP
48
16HP
16
8HP
24
8HP
26
10HP
28
10HP
30
10HP
32
8HP
34
10HP
36
10HP
38
10HP
40
10HP
42
12HP
44
12HP
46
12HP
48
12HP
manuals search engine
+
(A)
Total pipe length on each liquid side
m
=
=
=
=
=
=
Combined outdoor units (HP)
8HP
10HP
10HP
12HP
10HP
12HP
14HP
16HP
12HP
10HP
12HP
12HP
12HP
10HP
12HP
12HP
14HP
12HP
16HP
12HP
16HP
14HP
16HP
16HP
8HP
8HP
8HP
8HP
8HP
10HP
8HP
10HP
10HP
8HP
8HP
8HP
8HP
8HP
8HP
10HP
8HP
8HP
10HP
10HP
8HP
10HP
10HP
10HP
10HP
10HP
10HP
12HP
10HP
10HP
12HP
12HP
10HP
12HP
12HP
12HP
kg
kg
kg
122
Corrective amount of refrigerant
according to system horsepower
(C)
Additional amount of refrigerant pipe diameter on
each liquid side
kg
C (Corrective amount of refrigerant) (kg)
1.5
2.5
3.5
8.5
10.5
0.0
3.0
5.0
7.5
8.5
9.5
11.5
12.5
3.0
4.0
6.0
7.0
8.0
10.0
12.0
14.0
0.0
-4.0
-4.0
-2.0
0.0
-6.0
-6.0
-6.0
-6.0
-5.0
-4.0
-2.0
0.0
2.0
kg
kg
kg
kg
kg
kg
kg