Check Codes Displayed On Remote Controller And Smms-I Outdoor Unit (7-Segment Display On I/F Board) And Locations To Be Checked - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

8-4. Check Codes Displayed on Remote Controller and
SMMS-i Outdoor Unit (7-Segment Display on I/F
Board) and Locations to Be Checked
For other types of outdoor units, refer to their own service manuals.
Outdoor 7-segment display
Main
remote
Check
controller
code
E01
E02
E03
E04
E06
E06
E07
Downloaded from
www.Manualslib.com
Check code
Location
AI-NET central
of
control
detection
remote
Sub-code
controller
Remote
controller
Remote
controller
Indoor
unit
97
Indoor
unit
04
No. of indoor
I/F
units from
which signal is
received
normally
04
I/F
manuals search engine
Description
System status
Indoor-remote
Stop of
Communication between
controller
corresponding
indoor P.C. board and remote
communication
unit
controller is disrupted.
error
(detected at
remote
controller end)
Remote
Stop of
Signal cannot be transmitted
controller
corresponding
from remote controller to
transmission
unit
indoor unit.
error
Indoor-remote
Stop of
There is no communication
controller
corresponding
from remote controller
communication
unit
(including wireless) or
error
network adaptor.
(detected at
indoor end)
Indoor-outdoor
Stop of
Indoor unit is not receiving
communication
corresponding
signal from outdoor unit.
circuit error
unit
(detected at
indoor end)
Dropping out of
All stop
Indoor unit initially
indoor unit
communicating normally fails
to return signal for specified
length of time.
Indoor-outdoor
All stop
Signal cannot be transmitted
communication
from outdoor to indoor units
circuit error
for 30 seconds continuously.
(detected at
outdoor end)
178
Error detection
Check items (locations)
condition(s)
• Check remote controller
inter-unit tie cable (A/B).
• Check for broken wire or
connector bad contact.
• Check indoor power
supply.
• Check for defect in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
• Check internal
transmission circuit of
remote controller.
--- Replace remote
controller as necessary.
• Check remote controller
and network adaptor
wiring.
• Check order in which
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor termination
resistance setting (SW30,
Bit 2).
• Check power supply to
indoor unit.
(Is power turned on?)
• Check connection of
indoor-outdoor
communication cable.
• Check connection of
communication connectors
on indoor P.C. board.
• Check connection of
communication connectors
on outdoor P.C. board.
• Check for defect in indoor
P.C. board.
• Check for defect in outdoor
P.C. board (I/F).
• Check outdoor termination
resistance setting (SW30,
Bit 2).
• Check connection of
indoor-outdoor
communication circuit.

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map0804ht8zg-eMmy-map0804ht8z-eMmy-map1004ht8-eMmy-map1004ht8zg-eMmy-map1204ht8-eMmy-map1204ht8z-e ... Show all

Table of Contents