Precautions; Address Setup And Check Procedure - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

7-4. Address Setup
This product requires address setup before operation.
Follow this procedure for address setup.

7-4-1. Precautions

(1) Address setup is not performed simply by turning on the power supply.
(2) For indoor units, address setup can be done either by manual address setup or by automatic address setup:
Automatic address setup: Setup from SW15 on the interface PC board of the header unit
Manual address setup: Setup from the wired remote controller. (For details, refer to "7-4-3. Address Setup
Procedure.")
(3) Automatic setup usually takes about 5 minutes per line. In some cases, however, it may take up to 10 minutes.
(4) It is unnecessary to operate the air conditioner to achieve address setup.

7-4-2. Address Setup and Check Procedure

Procedure
1
2
3
4
5
6
Downloaded from
www.Manualslib.com
Item
Indoor unit power-on
Turn on the power of the indoor unit for the refrigerant line for which the address is to be set up.
Outdoor unit power-on
Turn on the power of all the outdoor units for the refrigerant line for which the address is to be
set up.
7-segment display
Check that "L08" is displayed on the 7-segment display [B] on the interface PC board of the
check
header unit in the system where the address is to be set up.
Address setup start
Confirm the items in "7-4-3. Address Setup Procedure," and then set up the address according
to the operation procedure.
(Be careful to note that the setup operation may differ in group control and central control
systems.)
Note:
The address cannot be set up if switches are not operated.
Display check after
• After address setup, "U1" " " is displayed on the 7-segment display.
setup
• For follower outdoor units, "U2" to "U4" are displayed on the 7-segment display [A].
• If an error code is displayed on the 7-segment display [B], remove the cause of the problem
referring to "8 TROUBLESHOOTING."
System information
Using the 7-segment display function, check the system information of the scheduled system.
check after setup
(This check is executed on the interface PC board of the header unit.)
After the above checks, return rotary switches SW01, SW02, and SW03 to 1/1/1.
Interface PC board
manuals search engine
Operation and check contents
Rotary switch setup
SW01
SW02
System capacity
1
2
Number of connected
1
3
outdoor units
Number of connected
1
4
indoor units
SW04
SW05
Push switches
D600 D601 D602 D603 D604
7-segment display
[A]
SW01 SW02 SW03
Rotary switches
124
7-segment display
SW03
[A]
[B]
[Number of
3
[H P]
horsepower]
3
[Number of units]
[ P]
[Number of
3
connected units]
SW15
7-segment display
[B]