10-3.Work procedure after Repair

When vacuuming in the repaired outdoor unit, follow the procedure described below.
<Work procedure>
(1) Fully open PMV1 and 2 and PMV4 (MMY-MAP1404 and MAP1604 only) in accordance with the table below.
Note: PMV full-opening operation via short-circuiting of the CN30 pins is automatically undone after 2 minutes,
causing the valves to fully close. To maintain fully open state, turn off the power switch of the outdoor unit
within 2 minutes of the short-circuiting of the CN30 pins.
(2) Be sure to perform vacuuming in from the three check joints shown in the diagram below (liquid pipe, discharge
pipe and suction pipe).
Downloaded from
www.Manualslib.com
SW12
Bit 1
Bit 2
Bit 3
Bit 4
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
PMV1
PMV2
(TE1)
PMV4
(TE2)
High-pressure sensor
(TL)
(SV3D)
Fusible
plug
Liquid tank
(SV3A)
Check valve
Liquid-side
Gas-side
Balance pipe
service valve
service valve
packed valve
manuals search engine
CN30
Short-circuit
PMV1 and 2 fully open for 2 minutes.
Short-circuit
PMV4 fully opens for 2 minutes.
M
Fan motor
Right-side
Main heat exchanger
Right-side sub-heat exchanger
Left-side
Main heat exchanger
Left-side sub-heat exchanger
(SV6)
SV
SV
(SV2)
Oil separator
SV
(SV41)
SV
SV
(SV42)
High-
(SV3C)
High-
(TD1)
pressure
(TD2)
pressure
SW
SW
(TK4)
Compressor
Compressor
1
2
(Inverter)
(Inverter)
(TK2)
(TK1)
Oil pipe
(TK5)
(SV3E)
(SV3F)
SV
254
PMV operation
Fan
(TO)
Check valve
Check valve
4-way valve
(TS1)
Low-pressure sensor
Accumulator
SV
(SV43)
High-
(TD3)
pressure
SW
Compressor
3
(Inverter)
(TK3)
(SV3B)
SV
Check valve

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mmy-map0804ht8zg-eMmy-map0804ht8z-eMmy-map1004ht8-eMmy-map1004ht8zg-eMmy-map1204ht8-eMmy-map1204ht8z-e ... Show all

Table of Contents