Power Peak-Cut Control (Extended); Specifications Of Display Relay Contact - Toshiba MMY-MAP0804HT8-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804HT8-E:
Table of Contents

Advertisement

<SW07 Bit 2 OFF (two-step control)>
Power peak-cut control is enabled as long as SW1, as shown on the wiring diagram, is ON (continuously).
Jumper wire
J16
Cut
Note 1: Specifications of display relay contact
• The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
<Electrical Rating>
220 to 240 VAC, 10 mA or more, 1 A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).

6-8-2. Power peak-cut Control (Extended)

Operation
An external power peak-cut control signal limits the peak capacity of the outdoor unit.
L1: Power peak-cut control indication lamp
SW1: Power peak-cut control ON switch*1
SW2: Power peak-cut control OFF switch*1
*1 The inputs of SW1 and SW2 can be either pulse (100 msec or wider) or step signals.
* Be sure to provide a contact for each terminal.
Extended power peak-cut control settings

Specifications of display relay contact

Indication lamp
L1
OFF
ON
ON
ON
Note 1: Specifications of display relay contact
• The terminal for display output ([Operation] terminal) must satisfy the following electrical rating.
<Electrical Rating>
220 to 240 VAC, 10 mA or more, 1 A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
When connecting a conductive load (e.g. relay coil) to the display relay load, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
The optional P.C. board should be connected to the header outdoor unit (U1).
Downloaded from
www.Manualslib.com
Input
SW1
OFF
0% (forced stop)
ON
100% (normal operation)
Header outdoor unit
Optional PCB
Outdoor unit
interface PCB
CN513
SW07
ON
OFF
1 2 3 4
Bit 2 ON
Connection cable
External power peak-cut control
signals
SW1
SW2
OFF
OFF
ON
OFF
OFF
ON
ON
ON
manuals search engine
SW07 Bit 1
Bit 1 OFF
60% capacity (upper limit regulated)
100% (normal operation)
L1: Display lamp suring power peak cut control
Locally procured
Display
TB1
relay
Shield wire
[OPERATION]
PJ17
TB2
COM
[ON]
ON
COM
[OFF]
OFF
Shield wire
For SW1 and SW2, be sure to provide
no-voltage contacts for each terminal.
OFF
100% (normal operation)
80% (upper limit regulated)
60% (upper limit regulated)
0% (forced stop)
111
Indicator relay
Bit 1 ON
Power
supply
L1
SW1
SW2
Peak capacity
I/F SW07 Bit 1
ON
100% (normal operation)
85% (upper limit regulated)
75% (upper limit regulated)
60% (upper limit regulated)
(L1)