9-4. Check Codes Displayed on Remote Controller and SMMS-u Outdoor Unit
(7-Segment Display on I/F Board) and Locations to Be Checked
For other types of outdoor units, refer to their own service manuals.
Check code
Main
Outdoor 7-segment display
remote
Check
Sub-code
controller
code
Detected indoor
unit No.
A01
A01
Detected indoor
unit No.
A02
A02
Detected indoor
unit No.
A04
A04
E01
E02
E03
E04
Location
Description
of
detection
Indoor unit
Flow switch
(M-HWM)
operation
trouble
Indoor unit
Water
(M-HWM)
temperature
decrease
trouble
Indoor unit
Activation of
(M-HWM)
water heat
exchanger frost
protection
Remote
Indoor-remote
controller
controller
communication
trouble
(detected at
remote
controller end)
Remote
Remote
controller
controller
transmission
trouble
Indoor unit
Indoor-remote
controller
communication
trouble
(detected at
indoor end)
Indoor unit
Indoor-outdoor
communication
circuit trouble
(detected at
indoor end)
Indoor unit (including Hot Water Module)
Check code detection
System status
condition(s)
All stop
When water flow rate is
reduced.
All stop
Water temperature
continued the low status
regardless of that the
water-heater and water
pump is operating.
All stop
Frost protection for water
heat exchanger is activated.
Stop of
Communication between
corresponding
indoor P.C. board and
unit
remote controller is
disrupted.
Stop of
Signal cannot be transmitted
corresponding
from remote controller to
unit
indoor unit.
Stop of
There is no communication
corresponding
from remote controller
unit
(including wireless) or
network adaptor.
Stop of
Indoor unit is not receiving
corresponding
signal from outdoor unit.
unit
– 54 –
Check items (locations)
• Check the pump.
• Check the strainer.
• Check the flow switch.
(Type, directtion of
attachment and point of
contact)
• Check the water
temperature.
• Check the heat insulator of
water pipes.
• Check the line heater
• Check the PMV coil and
PMV.
• Check the 2-way valve coil
and 2-way valve.
• Check remote controller
inter-unit tie cable (A/B).
• Check for broken wire or
connector bad contact.
• Check indoor power
supply.
• Check for failure in indoor
P.C. board.
• Check remote controller
address settings
(when two remote
controllers are in use).
• Check remote controller
P.C. board.
• Check internal
transmission circuit of
remote controller.
--- Replace remote
controller as necessary.
• Check remote controller
and network adaptor
wiring.
• Check order in which
power was turned on for
indoor and outdoor units.
• Check indoor address
setting.
• Check indoor-outdoor tie
cable.
• Check outdoor terminator
resistor setting (SW100,
Bit 2).