Address Setup; Precautions; Address Setup And Check Procedure - Toshiba MMY-MUP0961HT6P-UL Service Manual

Hide thumbs Also See for MMY-MUP0961HT6P-UL:
Table of Contents

Advertisement

7-4. Address Setup

This product requires address setup before operation.
Follow this procedure for address setup.

7-4-1. Precautions

(1) Address setup is not performed simply by turning on the power supply.
(2) For indoor units, address setup can be done either by manual address setup or by automatic address setup:
Automatic address setup: Setup from SW06 on the interface P.C. board of the header unit Manual address
setup: Setup from the wired remote controller. (For details, refer to "7-4-3. Address Setup Procedure.")
(3) Automatic setup usually takes about 5 minutes per line. In some cases, however, it may take up to 10 minutes.
(4) It is unnecessary to operate the air conditioner to achieve address setup.

7-4-2. Address Setup and Check Procedure

Procedure
Item
Header outdoor unit
1
setting
2
Indoor unit power-on
3
Outdoor unit power-on Turn on the power of all the outdoor units for the refrigerant line for which the address is to be set up.
7-segment display
4
check
5
Address setup start
Display check after
setup
6
Communication setting
start
7
Display check after
communication setup
8
System information
check after setup
9
Interface P.C. board
Turn on DIP switch 1 of SW101 on the header outdoor unit interface P.C.boards.
And, turn on DIP switch 2 of SW100.
Turn on the power of the indoor unit for the refrigerant line for which the address is to be set up.
Check that "L08" is displayed on the 7-segment display [B] on the interface PC board of the header
unit in the system where the address is to be set up.
Confirm the items in "7-4-3. Address Setup Procedure," and then set up the address according to the
operation procedure.
(Be careful to note that the setup operation may differ in group control and central control systems.)
Note:
The address cannot be set up if switches are not operated.
• After address setup, "U1" " " is displayed on the 7-segment display.
• For follower outdoor units, "U2" to "U5" are displayed on the 7-segment display [A].
• If a check code is displayed on the 7-segment display [B], remove the cause of the problem
referring to "8 TROUBLESHOOTING."
Confirm the items in "7-4-3. Address Setup Procedure," and then set up the
communication according to the operation procedure.
Note:
The address cannot be set up if switches are not operated.
• After communication setup, "c.c." "Fin" is displayed on the 7-segment display.
• If a unit that has already been set for communication is connected, it cannot be set correctly.
In this case, clear the communication settings and set again.
Using the 7-segment display function, check the system information of the scheduled system.
(This check is executed on the interface PC board of the header unit.)
SW01
System capacity
Number of connected
outdoor units
Number of connected
indoor units
Communication
Type
After the above checks, return rotary switches SW01, SW02, and SW03 to 1/1/1.
Push switch
7-segment
display [A]
- 110 -
Operation and check contents
Rotary switch setup
SW02
SW03
1
2
3
1
3
3
[Number of units]
1
4
3
connected units]
2
16
2
Type : 0=TCC-Link, 1=TU2C-Link
SW04
SW05
SW06
SW01
SW02
SW03
Rotary switches
7-segment display
[A]
[B]
[Number of
capacity]
[Number of
[Type]
7-segment
display [B]