Error/Operation Output - Toshiba MMY-MAP0804FT8(ZG)-E Service Manual

Multi type
Hide thumbs Also See for MMY-MAP0804FT8(ZG)-E:
Table of Contents

Advertisement

6-8-7. Error/Operation Output : TCB-PCIN4E
Operation
In-operation output: An in-operation indication signal is output as long as at least one indoor unit is in operation
in the line.
Error output: An error indication signal is output if an error occurs in at least one indoor/outdoor unit in the line.
Note 1: Output Relay (K1, K2, K3) Contact Specifications
• Output terminals (OUTPUT1, 2, 3) must satisfy the following electrical rating.
• When connecting a conductive load (e.g. relay coil) to loads K1, K2 and K3, insert a surge killer CR (for an AC
power supply) or a diode for preventing back electromotive force (for a DC power supply) on the bypass circuit.
<Electrical Rating>
220-240 VAC, 10 mA or more, 1A or less
24 VAC, 10 mA or more, 1 A or less (non-conductive load)
C1
Connector cable 1 (CN511)
CN511
Connector on Interface side (green)
K1,K2
Relays
L1
Error indication Lamp
L2
Operation indication Lamp
OUTPUT1
Error output
OUTPUT2
Operation output
PJ20
Connector on optional PCB side
TB1
Terminal block
The optional P.C. board should be connected to the header outdoor unit (U1).
AMP Air Conditioning
Header outdoor unit
Optional PCB
Outdoor unit
C1
interface PCB
SW16
CN511
PJ20
ON
OFF
1 2 3 4
Locally procured
(See "NOTE")
TB1
L1
1
K1
OUTPUT1
2
L2
3
K2
OUTPUT2
4
5
OUTPUT3
Shield
6
wire
– 116 –
www.ampair.co.uk | sales@ampair.co.uk
PS
PS

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents