Computer Link Operation (Pr. 117 To Pr. 124) - Mitsubishi Electric FR-F500 Instruction Manual

Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

(2) Set the desired frequencies and voltages in Pr. 100 to Pr. 109.
• The setting must satisfy the following relationship: F1≠F2≠F3≠F4≠F5≠Pr. 19 "base frequency".
If the set frequencies are the same, a write error occurs.
If any frequency setting is "9999", its point is ignored.
Note: 1. The V/F 5-point flexible characteristic functions for V/F control only.
2. The V/F 5-point flexible characteristic does not function when Pr. 60 is selected.
3. The frequency voltage setting should be equal to or less than the Pr. 3 and Pr. 19 settings.
4. Pr. 19 must be set. (When Pr. 19 = "9999", Pr. 71 cannot be set to "2" (5-point flexible V/F
characteristic).)
5. If "2" is set in Pr. 71, Pr. 47 and Pr. 113 do not function.
6. When "2" is set in Pr. 71, the electronic overcurrent protection is calculated for a standard motor.

4.2.39 Computer link operation (Pr. 117 to Pr. 124)

Pr. 117 "station number"
Pr. 118 "communication speed"
Pr. 119 "stop bit length/data length"
Pr. 120 "parity check presence/absence"
Pr. 121 "number of communication retries"
Pr. 122 "communication check time interval"
Pr. 123 "waiting time setting"
Pr. 124 "CR, LF presence/absence selection"
Used to perform required settings for RS-485 communication between the inverter and personal computer.
Using the inverter setup software (FR-SW0-SETUP-WE (or -WJ for Japanese version)), parameter setting,
monitoring, etc. can be done efficiently.
The motor can be run from the PU connector of the inverter using RS-485 communication.
Communication specifications
Conforming standard
Number of inverters connected
Communication speed
Control protocol
Communication method
Character system
Stop bit length
Terminator
Parity check
Check system
Sumcheck
Waiting time setting
RS-485
1:N (maximum 32 inverters)
Selected between 19200, 9600 and 4800bps
Asynchronous
Half-duplex
ASCII (7 bits/8 bits) selectable
Selectable between 1 bit and 2 bits.
CR/LF (presence/absence selectable)
Selected between presence (even/odd) or absence
Present
Selectable between presence or absence
104
PARAMETERS
4

Hide quick links:

Advertisement

Table of Contents
loading