4.2.8 Starting frequency (Pr. 13)

Pr. 13 "starting frequency"
You can set the starting frequency between 0 and 60Hz.
Set the starting frequency at which the start signal is switched on.
Parameter
Factory Setting
Number
13
0.5Hz
Note: The inverter will not start if the frequency setting signal is less than the value set in Pr. 13 "starting
frequency".
For example, when 5Hz is set in Pr. 13, the motor will start running when the frequency setting signal
reaches 5Hz.
Note that when the Pr. 13 setting is less than the Pr. 2 value, merely turning on the start
signal will start the motor running at the set frequency if the command frequency is not
input.
<Setting>
Setting Range
0 to 60Hz
Output frequency
CAUTION
68
PARAMETERS
Related parameters
Pr. 2 "minimum frequency"
(Hz)
60
Pr.13
0
Frequency setting signal (V)
Forward
ON
rotation
Time
4