Electronic Overcurrent Protection (Pr. 9) - Mitsubishi Electric FR-F500 Instruction Manual

Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

Note: 1. In S-shaped acceleration/deceleration pattern A (refer to page 74), the set time is a period
required to reach the base frequency set in Pr. 3.
• Acceleration/deceleration time calculation expression when the set frequency is the base
frequency or higher
4
T
t =
×
9
(Pr.3)
T: Acceleration/deceleration time setting (seconds)
f : Set frequency (Hz)
• Guideline for acceleration/deceleration time at the base frequency of 60Hz (0Hz to set
frequency)
Frequency setting (Hz)
Acceleration/
decelerationtime (seconds)
2. If the Pr. 20 setting is changed, the settings of calibration functions Pr. 903 and Pr. 905 (frequency
setting signal gains) remain unchanged. To adjust the gains, adjust calibration functions Pr. 903
and Pr. 905.
3. When the setting of Pr. 7, Pr. 8, Pr. 44 or Pr. 45 is "0", the acceleration/deceleration time is 0.04
seconds.
4. When the RT signal is on, the other second functions such as second torque boost are also
selected.
5. If the shortest acceleration/deceleration time is set, the actual motor acceleration/deceleration
time cannot be made shorter than the shortest acceleration/deceleration time determined by the
mechanical system's GD

4.2.6 Electronic overcurrent protection (Pr. 9)

Pr. 9 "electronic overcurrent protection"
Set the current of the electronic overcurrent protection to protect the motor from overheat. This feature
provides the optimum protective characteristics, including reduced motor cooling capability, at low speed.
Parameter
Factory Setting
Number
9
Rated output current*
*0.75K is set to 85% of the rated inverter current.
<Setting>
• Set the rated current [A] of the motor.
(Normally set the rated current value at 50Hz.)
• Setting of "0" makes the electronic overcurrent protection (motor protective function) invalid. (The inverter's
output transistor protective function is valid.)
• When using a Mitsubishi constant-torque motor, first set "1" in Pr. 71 to choose the 100% continuous torque
characteristic in the low-speed range. Then, set the rated motor current in Pr. 9.
Note: 1. When two or more motors are connected to the inverter, they cannot be protected by the
electronic overcurrent protection. Install an external thermal relay to each motor.
2. When a difference between the inverter and motor capacities is large and the setting is small, the
protective characteristics of the electronic overcurrent protection will be deteriorated. In this case,
use an external thermal relay.
3. A special motor cannot be protected by the electronic overcurrent protection. Use an external
thermal relay.
5
2
× f
+
9 T
2
60
5
5
15
15
2
and motor torque.
Setting Range
0 to 3600A
120
12
35
Related parameter
Pr. 71 "applied motor"
66
PARAMETERS