<Setting>
Refer to the following table and set the parameter as required:
Fast-Response
Current Limit
Pr. 156 Setting
...Activated
...Not activated
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
Driving
100
Regenerative
Driving
101
Regenerative
Note 1: When "Operation not continued for OL signal output" is selected, the "E.OLT" alarm code (stopped
by stall prevention) is displayed and operation stopped.
(Alarm stop display "E.OLT")
2: If the load is heavy, the lift is predetermined, or the acceleration/deceleration time is short, the stall
prevention may be activated and the motor not stopped in the preset acceleration/deceleration
time. Therefore, set optimum values to the Pr. 156 stall prevention operation level.
(When the output voltage reduces during stall prevention operation, an overcurrent trip will be less
liable to occur but the torque decreases. Set "0" in Pr. 154 when the torque may be reduced.)
Stall Prevention
...Activated
...Not activated
Acceleration
Constant speed
130
PARAMETERS
OL Signal Output
...Operation continued
...Operation not
Deceleration
continued (Note 1)