Mitsubishi Electric FR-F500 Instruction Manual page 200

Hide thumbs Also See for FR-F500:
Table of Contents

Advertisement

Operating
status
PU (FR-DU04
/FR-PU04)
Alarm
definition
Operating
Additional
status
display on
Alarm
parameter unit
definition
(FR-PU04)
Interactive
only
guidance
Protective/alarm functions
Ambient temperature
Ambient humidity
Storage temperature
(Note 2)
Ambience
Altitude, vibration
Note: 1. Jog operation may also be performed from the operation panel or parameter unit.
2. Temperature applicable for a short period in transit, etc.
1 signal can be selected from output frequency, motor current (steady or peak value), output
voltage, frequency setting, running speed, motor torque, overload, converter output voltage
(steady or peak value), electronic overcurrent protection load factor, input power, output power,
load meter and reference voltage output. Pulse train output (1440 pulses/sec./full scale) and
analog output (0 to 10VDC).
Alarm definition is displayed when protective function is activated. 8 alarm definitions are stored.
(Four alarm definitions are only displayed on the operation panel.)
Input terminal signal states, output terminal signal states, option fitting status, terminal
assignment status
Output voltage/current/frequency/cumulative ON time immediately before activation of
protective function
Operation guide and troubleshooting by help function
Overcurrent shut-off (during acceleration, deceleration, constant speed), regenerative
overvoltage shut-off, undervoltage, instantaneous power failure, overload shut-off (electronic
overcurrent protection), ground fault current, output short circuit, main circuit device overheat,
stall prevention, overload alarm, fin overheat, fan fault, option fault, parameter error, PU
disconnection, retry count exceeded, output phase failure, CPU error, 24VDC power output
short circuit, operation panel power supply short circuit
-10 ° C to +50 ° C (non-freezing, Variable Torque at 75K to 375K), -10 ° C to +40 ° C (non-freezing,
Variable Torque at 450K to 530K), -10 ° C to +40 ° C (non-freezing, Light Variable Torque at 75K
to 375K)
90%RH or less (non-condensing)
-20 ° C to +65 ° C
Indoors. (No corrosive and flammable gases, oil mist, dust and dirt.)
Maximum 1000m above sea level 5.9m/s
178
SPECIFICATIONS
2
{0.6G} or less (conforms to JIS C 0911)