Signal Loss or Loop Break Relay Operation

The following graph shows the loop break operation for a high alarm
relay.
Set
Reset
de-energized
Relay
LED
Relay
LED
Relay
LED
When the meter detects a break in the 4-20 mA loop, the relay will go to
one of the following selected actions:
1.
Turn on (Go to alarm condition)
2.
Turn off (Go to non-alarm condition)
3.
Ignore (Process as a low signal condition)
A5E31917845
Input
energized
off
on
Loop Break = Ignore
SITRANS RD300 – OPERATING INSTRUCTIONS
Loop Break = Off
Loop Break = On
Page 47