SITRANS RD300
Process Input
INPUTS
ACCURACY
TEMPERATURE
DRIFT
SIGNAL INPUT
CONDITIONING
MULTI-POINT
LINEARIZATION
PROGRAMMABLE
EXPONENT
ROUND H TANK
LOW-FLOW
CUTOFF
DECIMAL POINT
CALIBRATION
RANGE
INPUT
IMPEDANCE
INPUT
OVERLOAD
F4 DIGITAL INPUT
CONTACTS
F4 DIGITAL INPUT
LOGIC LEVELS
A5E31917845
Field selectable:
0-20, 4-20 mA, 10 V (0-5, 1-5, 0-10 V), Modbus PV
(Slave)
±0.03% of calibrated span ±1 count,
square root & programmable exponent accuracy range:
10-100% of calibrated span
0.005% of calibrated span/C max from 0 to 65C ambient,
0.01% of calibrated span/C max from -40 to 0C ambient
Linear, square root, programmable exponent, or round
horizontal tank volume calculation
2 to 32 points
1.0001 to 2.9999
Diameter & Length: 999.999 inch or cm calculates volume
in gallons or liters respectively.
0-999999 (0 disables cutoff function)
Up to five decimal places or none:
d. d dddd , d. d ddd , d. d dd , d. d d , d. d ,
Input
Minimum Span
Range
Input 1 & Input 2
4-20 mA 0.15 mA
10 V
0.01 V
An error message will appear if the input 1 and input 2
signals are too close together.
Voltage ranges: greater than 500 k
Current ranges: 50 - 100
impedance)
Current input protected by resettable fuse, 30 VDC max.
Fuse resets automatically after fault is removed.
3.3 VDC on contact. Connect normally open contacts
across F4 to COM.
Logic High: 3 to 5 VDC
Logic Low: 0 to 1.25 VDC
SITRANS RD300 – OPERATING INSTRUCTIONS
dddddd
or
(depending on resettable fuse
Page 97