Measured Value (Mv); Complex Measured Value (Cmv); Wye - ABB COM600 User Manual

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS755496
5.2.8.
Name
Type
mag
AnalogueValue
q
Quality
t
TimeStamp
5.2.9.
Name
Type
cVal.mag
AnalogueValue
q
Quality
t
TimeStamp
5.2.10.
Name
Type
phsA.cVal.mag
AnalogueValue
phsA.q
Quality
phsA.t
TimeStamp
phsB.cVal.mag
AnalogueValue
phsB.q
Quality
phsB.t
TimeStamp
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual

Measured value (MV)

Value/ Value
range

Complex measured value (CMV)

CMV is configured in the same way as MV. The only difference is that, instead of a mag
tag, there is a cVal node containing a mag tag in the OPC namespace structure.
Value/ Value
range

WYE

Value/ Value
range
Mandat-
Protection inform-
ory/Optional
ation element
M
CurrentValue
M
DNP status
M
<none> | Time of
occurence
Mandat-
Protocol informa-
ory/Optional
tion element
M
CurrentValue
M
DNP status
M
<none> | Time of
occurrence
Mandat-
Protocol informa-
ory/Optional
tion element
M
Phase A Current
Value
M
DNP status
M
<none> | Time of
occurrence
O
Phase B Current
Value
O
DNP status
O
<client provided if
none>
OPC data types
VT_R4
VT_I4
VT_DATE
OPC data type
VT_R4
VT_I4
VT_DATE
OPC data types
VT_R4
VT_I4
VT_DATE
VT_R4
VT_I4
VT_DATE