Controllable Single Point (Spc) - ABB COM600 User Manual

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

3.4.5.17.
34
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Scale and Unit
Multiplier
1...1000000000

Controllable single point (SPC)

Table 3.4.5.17-1 Configurable SPC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
SPC
Class
Addresses
Control Index
-1 to 65535
Default: -1
Indication Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Control Code Quali-
Momentary
fier
Pulse
Latch
Default: Momentary
Control Object
Default: Binary control output
block (12).
Control Variation
0 to 65535
Default: 1
Indication Object
Binary input (1, 2)
Binary output (10)
Default: Binary input (1, 2)
Description
Data object number for indication.
Multiplier for scaling decimal values.
Description
Common data class according to IEC
61850.
Control index.
Indication index.
Object number for control.
Variation for control.
Object number for indication.
1MRS755496