ABB COM600 User Manual page 60

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

CODE
23
24
Response Function Codes
0
129
130
OBJECT
Var
Obj
1
1
1
2
2
2
2
10
10
10
60
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
FUNCTION
Delay Measure-
ment
Record current
time
Confirm
Response
Unsolicited Mes-
sage
Supported objects
Table A1-3 Supported objects
Description
0
Binary Input - All
Variations
1
Binary Input
2
Binary Input with
Status
0
Binary Input
Change - All
Variations
1
Binary Input
Change without
Time
2
Binary Input
Change with
Time
3
Binary Input
Change with
Relative Time
0
Binary Output -
All Variations
1
Binary Output
2
Binary Output
Status
DESCRIPTION
Perform propagation delay meas-
urement
Used in a network application to
allow the Master station and the
Outstation to record their time at
the same instant
Message fragment confirmation
Response to requested message
Spontaneous message without
request
REQUEST
Qual
(slave must
Codes(hex)
parse)
Func Codes
(dec)
1
06
1
00,01,06
1
00,01,06
1
06,07,08
1
06,07,08
1
06,07,08
1
06,07,08
1
06
1
00,01,06
1MRS755496
Supported
Yes
Yes
Yes
Yes
Yes
RESPONSE
Qual Codes
(master must
(hex)
parse)
Func Codes
129, 130
00, 01
129, 130
00, 01
129, 130
17, 28
129, 130
17, 28
129, 130
17, 28
129, 130
00, 01

Advertisement

Table of Contents
loading