DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Table 3.4.3-1 DNP LAN Channel properties
Property / Para-
Value or Value range/ Default
meter
Basic
In Use
In use
Not in use
Default: In use
Protocol
DNP Slave over LAN interface
Communication
Port
Local Address
Default: 127.0.0.1
Communication
Control
Check Connection
True
Request
False
Default: False
Connection Type
Default: TCP/IP
Link Layer Confirma-
In use Not in use Default: In
tions Enabled
use
Maximum Message
50...249
Length
Default: 230
Test Function of
0...65535
Link Interval
Default: 500
Response Timeout
0...255
Default: 2
Test Function For
True
Link
False
Default: False

Configuring DNP LAN IED properties

Table 3.4.4-1 lists the configurable properties for DNP LAN IED and value ranges for
these properties. The actual configuration by using the SAB600 is performed as described
in 3.4.1, General about configuring objects.
Description
Specifies whether the channel is in use or
not.
Protocol
The IP address which is locally used.
Specifies if incoming connection requests
are checked.
ConnectionTypeDesc
Determines whether the link layer confirm-
ations are in use.
Maximum length of a data link fragment.
Delay in milliseconds between the test
function of link commands. If the value is
set to zero, the test function of a link com-
mand is not sent.
Specifies the time in seconds that the DNP
3.0 link waits for the end of the received
message.
Specifies if "Test Function for Link" is
enabled.