Measured Value (Mv) - ABB COM600 Series User Manual

Version 5.0, dnp 3.0 serial slave opc
Hide thumbs Also See for COM600 Series:
Table of Contents

Advertisement

1MRS755495
3.4.5.14.
COM600 series, Version 5.0
DNP 3.0 Serial Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Send All Updates
True
False
Default: False
Send As 16 Bit
Send as 32 bit value
Value
Send as 16 bit value
Default: Send as 16 bit value
Time And Type
Send as static data (always
Variation
without time)
Event without time
Event with time
Event with relative time (valid
for binary inputs only)
Default: Event with time

Measured value (MV)

Table 3.4.5.14-1 Configurable MV properties for OPC client
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
MV
Class
Addresses
Indication Index
0...65535
Default: 0
Common
Class
Class 0...3
Default: Class 3
Description
Object number for indication.
Defines if all changes in value are sent to
the master.
Defines if the value is sent as 16 or 32 bit
value.
Specifies the type of the timestamp a
message is sent with.
Description
Common data class according to IEC
61850.
Indication index.
Class of ASDU. Data sent from the slave
to the master can be assigned to four
classes. Data in class 1 is sent with higher
priority than data in class 3.
43