1MRS755496
CODE
1
2
Control Function Codes
3
4
5
6
Freeze Function Codes
7
8
9
10
11
12
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
FUNCTION
DESCRIPTION
Read
Request objects from outstation
Respond with requested objects
Write
Store the specified objects to out-
station.
Respond with status of operation
Select
Select the output point of outstation
Respond with status of control
point
Operate
Set the output that has previously
been selected
Respond with status of control
point
Direct operate
Set the output directly
Respond with status of control
point
Direct operate
Set the output directly
- no ack
No respond
Immediate
Copy the specified objects to
Freeze
freeze buffer
Respond with status of operation
Immediate
Copy the specified objects to
Freeze
freeze buffer
-no ack
No respond
Freeze and
Copy the specified objects to
Clear
freeze buffer and clear objects
Respond with status of operation
Freeze and
Copy the specified objects to
Clear
freeze buffer and clear objects
-no ack
No respond
Freeze with time
Copy the specified objects to
freeze buffer at specified time
Respond with status of operation
Freeze with time
Copy the specified objects to
freeze buffer at specified time
-no ack
No respond
Supported
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
71