3.4.5.13.
3.4.5.14.
32
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Integer status (INS)
Table 3.4.5.13-1 Configurable INS properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
INS
Class
Addresses
Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)
Integer controlled step position information (ISC)
Table 3.4.5.14-1 Configurable ISC properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
ISC
Class
Addresses
Control Index
-1 to 65535
Default: -1
Indication Index
-1 to 65535
Default: -1
Data Class Spe-
cific
Control Object
Default: Analog control output
block (41).
Control Variation
0 to 65535
Default: 2
Description
Common data class according to IEC
61850.
Index.
Object number for indication.
Description
Common data class according to IEC
61850.
Control index.
Indication index.
Object number for control.
Variation for control.
1MRS755496