ABB COM600 User Manual page 57

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS755496
Sends/Executes Control
Operations:
Latch Off
[ ] Never
Queue
[x] Never
Clean Queue
[x] Never
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES
ONLY:
Reports Binary Input Change Events when no specific
variation requested:
[ ] Never
[ ] Only time-tagged
[ ] Only non-time-tagged
[x] Configurable to send one or the other, depends on data
point init
Sends Unsolicited Responses:
[ ] Never
[x] Configurable, depends on data point initialization
[ ] Only certain objects
[ ] Sometimes (attach explanation)
[ ] ENABLE/DISABLE UNSOLICITED function codes supported
Default Counter Object/ Variation:
[ ] No Counters Reported
[x] Configurable, depends on data point initialization
[ ] Default Object________________________
[ ] Default Variation______________________
[ ] Point-by-point list attached
Sends Multi-Fragment Responses:
[x] Yes
[ ] No
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
[x] Always
[ ] Always
[ ] Always
Supported function codes
[ ] Sometimes
[ ] Sometimes
[ ] Sometimes
Reports time-tagged Binary Input Change Events when
no specific variation requested:
[ ] Never
[ ] Binary Input Change With Time
[ ] Binary Input Change With Relative Time
[x] Configurable, depends on data point initialization
Sends Static Data in Unsolicited Responses:
[X] Never
[ ] When Device Restarts (depends on data point initialization)
[ ] When Status Flags Change (depends on data point initializ-
ation)
No other options are permitted
Counters Roll Over at:
[ ] No Counters Reported
[ ] Configurable (attach explanation)
[ ] 16 bit
[x] 32 Bits, roll-over bits not set
[ ] Other Value__________________________________
[ ] Point-by-point list attached
[ ] Configurable
[ ] Configurable
[ ] Configurable