Configuring Dnp Lan Slave Opc Client Properties; Configuring Dnp Lan Channel Properties - ABB COM600 User Manual

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

3.4.2.
3.4.3.
20
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual

Configuring DNP LAN Slave OPC Client properties

Table 3.4.2-1 lists the configurable DNP LAN Slave OPC Client properties and value
ranges for them. The actual configuration by using SAB600 is performed as described
in 3.2, Overview of configuration.
Table 3.4.2-1 DNP LAN Slave OPC Client properties
Property / Para-
Value or Value range/ Default
meter
Basic
Maximum OPC
0...65535
Server Initialization
Default: 5
Time
Prog ID AE
ProgID DA
Time Zone Correc-
-720...720
tion
Default: 0
Station/Remote
Switch
Station/Remote
Do not check Station/Remote
Switch Handling
switch position.
Check Station/Remote switch
position.
Default: Do not check Sta-
tion/Remote switch position.
Station/Remote
Reject commands if position
Switch Error
bad or unknown.
Allow commands if position bad
or unknown.
Default: Reject commands if
position bad or unknown

Configuring DNP LAN Channel properties

The DNP LAN channel properties that can be configured and value ranges for them can
be found in Table 3.4.3-1. The actual configuration by using the SAB600 is performed
as described in 3.4.1, General about configuring objects.
Description
Specifies the maximum time in seconds
that any connected (configured) OPC
Server requires to retrieve all its initial
data.
Instance identification of diagnostic OPC
alarm and event server.
Instance identification of diagnostic OPC
data access server.
The value of this property in minutes is
added to the synchronization time received
from a DNP master.
Specifies if a position check for the station
remote switch is going to be made.
Defines command handling if the position
is bad or unknown.