ABB COM600 User Manual page 22

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

22
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Table 3.4.4-1 DNP LAN IED properties
Name
Value/Value range
Basic
Diagnostics Enabled
True
False
Default: False
In Use
In use
Not in use
Default: In use
Subset
Subset 2
Subset 3
Default: Subset 2
Addresses
Internet Address
Default: 127.0.0.1
Master Address
0...65535
Default: 1
Slave Address
0...65535
Default: 1
Communication
Control
Sending Messages
True
False
Default: True
Use Variations
True
False
Default: True
Command Hand-
ling
Command Address
0...65535
Default: 32000
Execute Waiting
0...65
Time after Select
Default: 30
Lengths
Description
Specifies whether diagnostic AE events
are sent for the station.
Defines if the IED is in use or not.
Defines the subset level that is currently
used.
The IP address of the remote host.
The station address of the master station.
The station address of the DNP 3.0 slave
station.
Sending messages while waiting for a
confirmation.
Variations in response messages.
The object address of the bitstream pro-
cess object.
The maximum time in seconds that the
slave waits for an execute command after
receiving an operator command.
1MRS755496