Logical Node Name Plate (Lpl); Measured Value (Mv) - ABB COM600 User Manual

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS755496
3.4.5.15.
3.4.5.16.
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual
Property/ Para-
Value or Value range/ Default
meter
Indication Object
Analog input (30, 32)
Analog output (40)
Default: Analog input (30, 32)

Logical Node Name Plate (LPL)

Table 3.4.5.15-1 Configurable LPL properties
Property/ Para-
Value or Value range/ Default
meter
Basic
61850 Data Object
LPL
Data Class Spe-
cific
Serial number
User defined.
Default: ABB123456789
Software Revision
Default: 1.0
Vendor
ABB

Measured value (MV)

Table 3.4.5.16-1 Configurable MV properties
Property/ Para-
Value or Value range/ Default
meter
Basic
Common Data
MV
Class
Addresses
Index
-1 to 65535
Default: -1
Sub-Type
Subtype
Simple
Data Class Spe-
cific
Description
Object number for indication.
Description
61850 Data Object
Text string describing serial number.
Text string describing software revision.
Text string describing vendor.
Description
Common data class according to IEC
61850.
Indication index.
MV Sub-type
33