Appendix 1 - ABB COM600 User Manual

Station automation, 3.4, dnp 3.0 lan/wan slave (opc)
Hide thumbs Also See for COM600:
Table of Contents

Advertisement

1MRS755496
DNP V3.00DEVICE PROFILE DOCUMENT
Vendor Name: ABB Oy Substation Automation Products
Device Name: COM600
Highest DNP Level Supported:
For Requests: Subset Level 2
For Responses: Subset Level 2
Notable objects, functions, and/or qualifiers supported in
addition to the Highest DNP Levels Supported
(the complete list is described in the attached table):
Additions to level 2 are shaded in the accompanying imple-
mentation tables.
Maximum Data Link Frame Size (octets):
Transmitted: 58...292
Received: (must be 292)
Maximum Data Link Re-tries:
[ ] None
[ ] Fixed at _______________________
[x] Configurable, range 0 to 10
Requires Data Link Layer Confirmation:
[ ] Never
[ ] Always
[ ] Sometimes If 'Sometimes', when? ______________________________________________
[x] Configurable
Requires Application Layer Confirmation:
[ ] Never
[ ] Always (not recommended)
[ ] When reporting Event Data (Slave devices only)
[ ] When sending multi-fragment responses (Slave devices only)
[ ] Sometimes. If 'Sometimes', when? ______________________________________________
Station Automation COM600 3.4
DNP 3.0 LAN/WAN Slave (OPC) User's Manual

Appendix 1

Device profile
Table A1-1 Device profile describing the implementation of DNP V3.00 slave pro-
tocol in COM600 SUBSET 2: the default subset
Device Function:
[ ] Master [x] Slave
Maximum Application Fragment Size (octets):
Transmitted: 255...2048
Received : 2048
Maximum Application Layer Re-tries:
[ ] None
[x] Configurable, range 0 to 5
55