Boolean To Integer Conversion With Logical Node Representation, 16 Bit Btigapc; Identification; Application - ABB 650 series Applications Manual

Hide thumbs Also See for 650 series:
Table of Contents

Advertisement

Section 9
Logic
9.9
9.9.1
9.9.2
184
Name of input
Type
IN1
BOOLEAN
IN2
BOOLEAN
IN3
BOOLEAN
IN4
BOOLEAN
IN5
BOOLEAN
IN6
BOOLEAN
IN7
BOOLEAN
IN8
BOOLEAN
IN9
BOOLEAN
IN10
BOOLEAN
IN11
BOOLEAN
IN12
BOOLEAN
IN13
BOOLEAN
IN14
BOOLEAN
IN15
BOOLEAN
IN16
BOOLEAN
The sum of the numbers in column "Value when activated" when all INx (where
1≤x≤16) are active that is=1; is 65535. 65535 is the highest boolean value that can
be converted to an integer by the B16I function block.
Boolean to integer conversion with logical node
representation, 16 bit BTIGAPC

Identification

Function description
Boolean to integer conversion with
logical node representation, 16 bit

Application

Boolean to integer conversion with logical node representation, 16 bit (BTIGAPC)
is used to transform a set of 16 binary (logical) signals into an integer. BTIGAPC
has a logical node mapping in IEC 61850.
Default
Description
0
Input 1
0
Input 2
0
Input 3
0
Input 4
0
Input 5
0
Input 6
0
Input 7
0
Input 8
0
Input 9
0
Input 10
0
Input 11
0
Input 12
0
Input 13
0
Input 14
0
Input 15
0
Input 16
IEC 61850
IEC 60617
identification
identification
BTIGAPC
1MRK 511 423-UEN A
Value when
Value when
activated
deactivated
1
0
2
0
4
0
8
0
16
0
32
0
64
0
128
0
256
0
512
0
1024
0
2048
0
4096
0
8192
0
16384
0
32768
0
SEMOD175753-1 v4
SEMOD175757-2 v5
ANSI/IEEE C37.2
device number
-
-
SEMOD175849-4 v6
Bay control REC650 2.2 IEC
Application manual