YASKAWA L1000A Quick Start Manual page 45

Ac drive for elevator applications
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Digital Operator AL
FLT
Output Current
Error
(SE3)
Brake Response
Error
(SE4)
Motor Pull Out or
Step Out Detection
(STo)
Position Lock
Error
(SvE)
DC Bus
Undervoltage
(Uv1)
Control Power
Supply
Undervoltage
(Uv2)
Soft Charge
Circuit Fault
(Uv3)
Operator Programing Errors
An Operator Programming Error (
is inappropriate. When an oPE error is displayed, press the ENTER button to display U1-18. Monitor U1-18 will display
the parameter that is causing the oPE error.
Digital Operator
(oPE01) Drive capacity and the value set to o2-04 do not match.
(oPE02) Parameters were set outside the allowable setting range.
A contradictory setting is assigned to multi-function contact
inputs H1-03 through to H1-08.
• The same function is assigned to two multi-function inputs.
• Excludes "Brake feedback" and "Brake feedback 2."
• Brake Feedback (H1- = 79) or Brake Feedback 2 (H1-
(oPE03)
 = 5B) function is assigned to three or more multi-
function inputs.
• Motor contactor feedback and Motor contactor feedback 2
(56 vs. 5A) are selected simultaneously.
The source of the Up/Down command or speed reference is
assigned to option card (b1-01 or b1-02 = 3), but no option
(oPE05)
card is installed.
A control mode has been selected that requires an encoder to
(oPE06)
be installed, but no encoder is installed (A1-02 = 3 or 7).
H3-02 and H3-10 are set to the same value (this excludes
(oPE07)
settings 0 and F).
YASKAWA ELECTRIC TOEP C710616 33G AC Drive L1000A - Quick Start Guide
Possible Cause
The output current was lower than 25% of the motor
no-load current during operation.
The brake close command was set but he status of the
brake feedback signal did not change.
• The wrong motor code has been set (YASKAWA
motors only).
• Load is too heavy.
• Accel/decel ramp is too short.
The motor turned too much out of the target position
during position lock operation.
• The voltage in the DC bus fell below the undervoltage
detection level (L2-05).
• The power supply failed or one input phase has been
lost.
• The power supply is too weak.
The control power supply does not have enough
voltage.
The charge circuit for the DC bus is broken.
) occurs when an inapplicable parameter is set or an individual parameter setting
Possible Cause
Corrective Action
• Check the motor wiring.
• Check the motor contactor and the contactor
sequence. Make sure does not open during operation.
• Make sure the brake works properly.
• Check the brake feedback input.
• Enter the correct motor code for the PM being used
into the E5 parameters.
• For special-purpose motors, enter the correct data to
all E5 parameters according to the Test Report
provided for the motor.
• Reduce the load.
• Increase the motor or drive capacity.
• Increase the acceleration and deceleration times (C1-
01 through C1-08).
• Increase the jerk setting in C2-02 through C2-05
(decrease if o1-03 > 3).
• Check the speed control loop parameters (C5-)
and adjust if necessary.
• Check the position lock settings (S3-01/S3-02/S3-03).
• Check the speed feedback signal for noise.
• Check the power supply.
• Make sure that the power supply can provide enough
voltage.
• Cycle power to the drive. Check if the fault reoccurs.
• Replace the drive if the fault continues to occur.
• Cycle power to the drive and see if the fault reoccurs.
• Replace the drive if the fault reoccurs.
Corrective Action
Set to o2-04 to the correct value.
Set parameters to the proper values.
• Fix any incorrect settings.
• Refer to the Technical Manual for more details.
• Install the required option card.
• Correct the values set to b1-01 and b1-02.
• Connect an encoder.
• Correct the value set to A1-02.
• Fix any incorrect settings.
• Refer to the Technical Manual for more details.
8 Troubleshooting
EN 45

Advertisement

Table of Contents
loading

Table of Contents