1 Safety Instructions and General Warnings
Use appropriate equipment for residual current monitoring / detection (RCM / RCD).
This drive can cause a residual current with a DC component in the protective earthing conductor. Where a residual
current operated protective or monitoring device is used for protection in case of direct or indirect contact, always use
an RCM or RCD of type B according to IEC/EN 60755.
Stay clear of the motor during rotational Auto-Tuning. The motor may start operating suddenly.
During automatic starting of equipment, the machine may start moving suddenly, which could result in death or serious
injury.
System may start unexpectedly upon application of power, resulting in death or serious injury.
Clear all personnel from the drive, motor, and machine area before applying power. Secure covers, couplings, shaft
keys, and machine loads before applying power to the drive.
Use parameter S1-12 to enable/disable automatic switching of the Motor Contactor Control output signal
during Auto-Tuning.
When using setting S1-12 = 1 or 2, ensure that the multi-function output terminals are properly wired and in the correct
state before setting parameter S1-12.
Failure to comply could result in damage to the drive, serious injury or death.
Drive Short-Circuit Current Rating
Install adequate branch circuit protection according to applicable local codes and this Installation Manual.
Failure to comply could result in fire and damage to the drive or injury to personnel.
The device is suitable for use on a circuit capable of delivering not more than 100,000 RMS symmetrical amperes, 240
Vac maximum (200 V class) and 480 Vac maximum (400 V class), and 600 Vac maximum (600 V class) when
protected by branch circuit protection devices specified in this manual.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply before applying power.
Do not use improper combustible materials in drive installation, repair or maintenance.
Failure to comply could result in death or serious injury by fire. Attach the drive or braking resistors to metal or other
noncombustible material.
Do not connect the AC power line to the output motor terminals of the drive.
Failure to comply could result in death or serious injury by fire as a result of drive damage from line voltage
application to output terminals.
• Do not connect AC line power to output terminals U, V, and W.
• Make sure that the power supply lines are connected to main circuit input terminals R/L1, S/L2, T/L3 (or R/L1 and S/
L2 for single-phase power).
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating of electrical connections.
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive falling.
EN 6
WARNING
Sudden Movement Hazard
Fire Hazard
CAUTION
Crush Hazard