Up and Down Commands and Speed Reference Selection
Speed Reference Selection
Parameter b1-01 determines the source of the speed reference.
b1-01
Reference source
0 (default)
Operator keypad (Digital inputs)
1
Analog input
2
Serial Communication
3
Option Board
<1> If source of the speed reference is assigned to the control terminals (b1-01 = 1), then d1-18 will automatically be set to 0 (so that the drive uses
multi-speed references d1-01 to d1-08) by the drive's internal processing.
<2> If the speed reference selection in d1-18 is set so that either the high speed reference has priority (d1-18 = 1), or so that the leveling speed has
priority (d1-18 = 2), then the drive will look to the multi-function input terminals for the speed reference.
Up / Down Command Source Selection
The input source for the Up and Down signal can be selected in parameter b1-02.
b1-02
Up/Down source
0
Operator keypad
1 (default)
Digital inputs
2
Serial Communication
3
Option Board
Travel Start and Stop
Travel Start
To start the elevator in the up or down direction, the following conditions must be fulfilled:
• A speed reference greater than zero must be selected.
• The Safe Disable signals at terminals H1 and H2 must both be closed.
• An Up or Down Signal must be set at the source specified in b1-02.
Travel Stop
The drive stops under the following conditions:
• The Up or Down command is cleared.
• d1-18 is set to 1 or 2 and the Up/Down or Leveling Speed signal (H1- = 53) is cleared.
• d1-18 is set to 3 and all speed inputs are cleared.
• A fault occurs. The stopping method depends on the fault occurred and certain parameter settings.
• The Safe Disable inputs are opened or a Base Block signal is input. In this case the brake is applied immediately and
the drive output shuts off.
YASKAWA ELECTRIC TOEP C710616 33G AC Drive L1000A - Quick Start Guide
Set the speed references in the d1- parameters and use digital inputs to switch over
between different reference values.
Apply the speed reference signal to terminal A1 or A2.
<1>
Serial Communications using the RS422/485 port
<2>
Communications option card
<2>
RUN and STOP keys on the operator
Terminal S1: Run in the Up direction
Terminal S2: Run in the Down direction
Serial Communications using the RS422/485 port
Communications option card
Speed Reference Input
Up/Down Command Input
5 Start Up
EN 29