Installing Input Fuses
NOTICE: If a fuse is blown or a Residual Current Device (RCD) is tripped, check the wiring and the selection of the peripheral devices
to identify the cause. Contact YASKAWA before restarting the drive or the peripheral devices if the cause cannot be identified.
Factory Recommended Branch Circuit Protection
YASKAWA recommends installing one of the following types of branch circuit protection to maintain compliance with
UL508C. Semiconductor protective type fuses are preferred. Alternate branch circuit protection devices are also listed
below.
Drive Model
AC Drive Input
CIMR-L
20008
20011
20018
20025
20033
20047
20060
20075
20085
20115
20145
20180
20215
20283
20346
20415
40005
40006
40009
40015
40018
40024
40031
40039
40045
40060
40075
40091
40112
40150
40180
40216
<1> Maximum MCCB Rating is 15 A, or 200% of drive input current rating, whichever is larger. MCCB voltage rating must be 600 Vac or greater.
<2> Maximum Time Delay fuse is 175% of drive input current rating. This covers any Class CC, J or T class fuse.
<3> Maximum Non-time Delay fuse is 300% of drive input current rating. This covers any CC, J or T class fuse.
<4> When using semiconductor fuses, Bussmann FWH and FWP are required for UL compliance. Select FWH for 200 V Class and 400 V Class
models and FWP fuses for 600 V models.
<5> Class L fuse is also approved for this rating.
YASKAWA ELECTRIC TOEP C710616 33G AC Drive L1000A - Quick Start Guide
L1000A in Heavy Duty Mode (C6-01 = 0)
MCCB Rating
Amps
Amps
Three-Phase 200 V Class
7.5
15
11
20
18.9
35
28
50
37
60
52
100
68
125
80
150
82
150
111
200
136
250
164
300
200
400
271
500
324
600
394
700
Three-Phase 400 V Class
4.4
15
6
15
10.4
20
15
30
20
40
29
50
39
75
47
75
43
75
58
100
71
125
86
150
105
175
142
225
170
250
207
350
Time Delay Fuse
Rating Amps
<1>
<2>
12
17.5
30
40
60
90
110
125
125
175
225
250
350
450
500
600
7
10
17.5
25
35
50
60
75
75
100
110
150
175
225
250
350
11 UL Standards
Bussmann
Non-time Delay
Semiconductor
Fuse Rating
Fuse Rating (Fuse
Amps
<3>
Ampere)
20
FWH-70B (70)
30
FWH-70B (70)
50
FWH-90B (90)
75
FWH-100B (100)
100
FWH-200B (200)
150
FWH-200B (200)
200
FWH-200B (200)
225
FWH-300A (300)
225
FWH-300A (300)
250
FWH-350A (350)
350
FWH-400A (400)
450
FWH-400A (400)
600
FWH-600A (600)
800
FWH-700A (700)
900
FWH-800A (800)
<5>
1100
FWH-1000A (1000)
<5>
12
FWH-70B (70)
17.5
FWH-70B (70)
30
FWH-90B (90)
40
FWH-80B (80)
60
FWH-100B (100)
80
FWH-125B (125)
110
FWH-200B (200)
125
FWH-250A (250)
125
FWH-250A (250)
150
FWH-250A (250)
200
FWH-250A (250)
250
FWH-250A (250)
300
FWH-350A (350)
400
FWH-400A (400)
500
FWH-500A (500)
600
FWH-600A (600)
<4>
EN 59