YASKAWA L1000A Quick Start Manual page 33

Ac drive for elevator applications
Hide thumbs Also See for L1000A:
Table of Contents

Advertisement

Brake Sequence
The figure below shows the brake sequence and parameters that can be used for adjustment.
Up/Down
Brake Control Output
Inspection Operation
Start in Inspection Mode
Inspection operation is performed when an Up or Down signal is input while one of the conditions below is true.
• Parameter d1-18 is set to 0 or 3 and the selected speed is higher than d1-28 but lower than d1-29.
• Parameter d1-18 is set to 1 or 2 and a digital input programmed for Inspection Operation Speed (H1- = 54) is
enabled.
The start is performed using the same acceleration characteristics, brake sequence and contactor sequence like in normal
operation. The carrier frequency is set to 2 kHz during Inspection Operation but can be changed using parameter C6-21.
Stop in Inspection Mode
To stop the drive in Inspection Mode either remove the Up or Down signal or unselect the Inspection Operation Speed
Reference (conditions listed for Start in Inspection Mode must become untrue).
The stop can be performed using a deceleration ramp, depending on the setting of parameter C1-15 (Inspection Operation
Deceleration Ramp).
• If C1-15 = 0, the drive immediately applies the brake, shuts off the drive output and opens the motor contactor.
• If C1-15 > 0, the drive decelerates to stop, applies the brake, shuts the output off and opens the motor contactor.
YASKAWA ELECTRIC TOEP C710616 33G AC Drive L1000A - Quick Start Guide
S1-04
DC Injection/
Position Lock
Time at Start
Speed
RUN
Selected Speed
Leveling
Speed
Zero Speed
Level S1-01
5 Start Up
S1-05
DC Injection/
Position Lock
at Stop
Enabled
EN 33

Advertisement

Table of Contents
loading

Table of Contents