PRECAUTIONS

Grounding Requirements

The system grounding must have a specific ground resistance and AC noise level, and is to be connected
to a predetermined terminal in the PBX. Standard grounding requirements are as shown below:
• Communication grounding
• Protective ground for Chassis: Less than 10 Ω
NOTE:
The AC ripple on these various grounds should be less than 0.5 Vp-p.
Grounding circuit continuity is vital for safe operation of telecommunication equipment.
Never operate this equipment with the grounding conductor disconnected.
The following specific requirements apply to ground wiring.
Install an equipment-grounding conductor that is at least as large as the ungrounded branch-supply
conductors as part of the circuit that supplies the PBX. Bare, covered, or insulated grounding
conductors are acceptable. Individually covered or insulated equipment grounding conductors shall
have a continuous outer finish that is either green, or green with one or more yellow stripes. The
equipment grounding connector is to be connected to ground at the service equipment.
The attachment-plug receptacles near the PBX are all to be of a grounding type, and the equipment
grounding conductors serving these receptacles are to be connected to earth ground at the service
equipment.
: Less than 10 Ω
CAUTION