Characteristic Values - Gossen MetraWatt ProFiTEST C-GB int. Operating Instructions Manual

Test instrument per din vde 0100
Table of Contents

Advertisement

9

Characteristic Values

Measuring Range
Function Measured Quantity
(display range)
0 ... 99.9 V
U
L–PE
100 ... 300 V
U
/ U
U
N–PE
L–N
(0 ... 600 V)
L–PE
U
N–PE
15.0 ... 99.9 Hz
f
100 ... 650 Hz
0 ... 99.9 V
U
U
100 ... 500 V
3~
(0 ... 600 V)
U
0 ... 99.9 V
IN
R
/ I
= 10 mA
10 ... 9.99 k
N
E
3  ... 999 
R
/ I
= 30 mA
N
E
1 k ... 6.40 k
1 ... 999 
R
/ I
= 100 mA
N
E
0.3  ... 99.9 
R
/ I
= 300 mA
N
100  ... 640 
E
0.2  ... 99.9 
R
/ I
= 500 mA
N
100  ... 380 
E
I
I
/ I
= 10 mA
3.0 ... 13.0 mA
N
I
/ I
= 30 mA
9.0 ... 39.0 mA
N
I
/ I
= 100 mA
30 ... 130 mA
N
I
/ I
= 300 mA
90 ... 390 mA
N
I
/ I
= 500 mA
150 ... 650 mA
N
U
/ U
= 25 V
0 ... 25.0 V
I
L
U
/ U
= 50 V
0 ... 50.0 V
I
L
0 ... 99.9 ms
t
(I
/5 · I
)
N
N
T
100 ... 999 ms
0 ... 0.49 
0.5 ... 9.99 
Z
Loop
10.0 ... 30.0 
Z
Loop
0 ... 99.9 
Z
15 mA
100 ... 250 
Loop
0 ... 0.49 
0.5 ... 9.99 
10.0 ... 99.9 
R
R
E
E
100 ... 999 
1.00 k ... 9.99 k
GMC-I Messtechnik GmbH
Input Impedance /
Resolution
Nominal Values
Test Current
0.1 V
1 V
500 k
0.1 Hz
500 k
1 Hz
0.1 V
1 V
500 k
0.1 V
0.3 · I
N
10 
3 
10 
1
0.3 ... 1.3 · I
N
U
0.3 
N
1 
U
N
0.2 
1 
f
N
3.0 ... 13.0 mA
0.1 mA
U
L
9.0 ... 39.0 mA
I
= 10/30/100/
1 mA
30 ... 130 mA
N
300/500 mA
1 mA
90 ... 390 mA
1 mA
150 ... 650 mA
0.1 V
same as I
0.1 ms
1.05 · I
/ 5 · I
N
N
1 ms
10 m
10 m
740 mA
100 m
U
N
100 m
15 mA
1 
U
N
10 m
740 mA
10 m
740 mA
f
N
10 m
400 mA
100 m
40 mA
1 
4 mA
Intrinsic uncertainty
(2% of rdg. + 2 d)
(0.1% of rdg. + 1 d)
(2% of rdg. + 2 d)
+(12.5% of rdg. + 2 d)
+(2.5% of rdg. – 2 d)
= 120 V
= 230 V
= 50 Hz
= 25/50 V
(5% of rdg. + 2 d)
+(12.5% of rdg. + 2 d)
+(2.5% of rdg. – 2 d)
3 ms
5 d
(6% of rdg. + 3 d)
(6% of rdg. + 3 d)
= 120 V
(6% of rdg. + 5 d)
(6% of rdg. + 3 d)
= 230 V
5 d
(6% of rdg. + 3 d)
= 50 Hz
(4% of rdg. + 3 d)
(4% of rdg. + 3 d)
(4% of rdg. + 3 d)
Nominal Range of
Measuring
Use
uncertainty
(4% rdg. + 3 d)
108 ... 253 V
(0.2% rdg. + 1 d)
15 ... 70 Hz
(4% rdg. + 3 d)
108 ... 440 V
5 ... 70 V
+15% rdg. + 2 d
Calculated Value
3.0 ... 13.0 mA
9.0 ... 39.0 mA
(8% rdg. +2 d)
30 ... 130 mA
90 ... 390 mA
150 ... 650 mA
0 ... 25.0 V
+15% rdg.+2 d
0 ... 50.0 V
4 ms
0 ... 1000 ms
0.25 ... 0.49 
(15% of rdg. + 5 d)
0.50 ... 9.99 
(10% of rdg. + 5 d)
10.0 ... 30.0 
(10% of rdg. + 5 d)
0.50 ... 99.9 
(15% of rdg.+10 d)
100 ... 250 
(10% of rdg.+10 d)
0.25  ... 0.49 
(15% of rdg. + 5 d)
0.50  ... 9.99 
(10% of rdg. + 5 d)
10.0  ... 99.9 
(8% of rdg. + 5 d)
100  ...999 
(8% of rdg. + 5 d)
(8% of rdg. + 5 d)
1 k ...9.990 k