11.3 Table of Minimum Display Values for Short-Circuit Current for the Determination of Current Ratings for Various Fuses and Circuit Breakers
for Systems with a Nominal Voltage of U
Low-Voltage Fuses in Accordance with
the DIN VDE 0636 Series of Standards
Characteristic gL, gG, gM
Nominal
Breaking Current, 5 s
Current
I
[A]
N
Limit Value
Min. Display
[A]
[A]
2
9.2
10
3
14.1
16
4
19
22
6
27
30
8
37
41
10
47
52
13
56
62
16
65
73
20
85
95
25
110
124
32
150
171
35
173
199
40
190
219
50
260
305
63
320
381
80
440
541
100
580
741
125
750
1.01 k
160
930
1.32 k
Example
➜
Display value 90.4 A
next smallest value for characteristic B circuit
➜
breaker from table: 85 A
rated current (I
max. 16 A.
GMC-I Messtechnik GmbH
=230/400 V
N
Characteristic B/E
(previously L)
Breaking Current, 0.4 s
Breaking Current,
5 x I
(< 0.2 s / 0.4 s)
N
Limit Value
Min. Display
Limit Value
[A]
[A]
[A]
16
18
10
24
27
15
32
35
20
47
52
30
65
73
40
82
92
50
98
110
65
107
121
80
145
165
100
180
207
125
265
311
160
295
349
175
310
368
200
460
569
250
550
697
315
) for the protective device is
N
with protective Circuit Breaker and Circuit Breaker
Characteristic C
(previously G, U)
Breaking Current,
10 x I
(< 0.2 s / 0.4 s)
N
Min. Display
Limit Value
Min. Display
[A]
[A]
[A]
11
20
23
17
30
33
23
40
44
33
60
67
44
80
90
56
100
113
73
130
148
90
160
183
113
200
231
142
250
292
183
320
381
201
350
420
231
400
487
292
500
625
375
630
816
Characteristic D
Characteristic K
Breaking Current,
Breaking Current,
20 x I
(< 0.2 s / 0.4 s)
12 x I
N
Limit Value
Min. Display
Limit Value
[A]
[A]
[A]
40
44
24
60
67
36
80
90
48
120
136
72
160
183
96
200
231
120
260
305
156
320
381
192
400
487
240
500
625
300
640
831
384
700
925
420
800
1.09 k
480
1000
1.45 k
600
1260
1.98 k
756
960
1200
1440
1920
(< 0.1 s)
N
Min. Display
[A]
27
40
53
81
108
136
178
221
280
356
465
514
596
771
1.02 k
1.37 k
1.85 k
2.42 k
3.90 k
35