Application
General ly, electrical power system engineers calculate the
></R ratios of circuit rather than power factor. The procedures
for calcu lating short-circuit current and X/R ratios a re de
scribed in Publication G ET-3 550.
Oscillogram of typical short circuit
Asymmetrical ac waveform
The fi g u res below show the initial fault current displacement
of a pure circuit (sym metrical) and a reactive circuit with a
high X/R ratio. The actua l current d isplacement of a reac
tive circuit depends on the exact moment the short circuit is
a ppl ies. There is a simple relationship between power factor
and X/R of a faulted circuit:
z
R
PF = - x 100
And: Z
R
+
Therefore PF =
PF = Power factor, %
R = Resistance i n ohms
I nterrupting Rati ngs - Sta ndard A n d Hi-Break® Brea kers
Power Break® I I brea kers a re available i n two classifications
of interrupting rati ngs: Standard and H i-Break breakers. All
ratings a re without the need for external fuses or current
l i miters. Hi-B reak b reakers' interrupting rati ngs a re for those
circuits with unusually high levels of available fa ult current.
46
Envelopes o f peaks a r e not
symmetri c a l about zero axis
Zero axis
+
(X JZ
=
x 100
Z
I m pedance i n ohms
=
>< = Reactance i n ohms
Table 46.1
Interrupting Rating Breaker Performance I n RMS Symmetrical kA
U L 489
50/60 Hz
800A
Standard
240V
65
480V
65
600V
50
H i-Break'"'
240V
100
480V
100
65
600V
Short Time
25
10 5 sec.)
IEC 947 - 2 Ratings
415V, 50/60 Hz
leu
-
lcs
-
lew (1 sec)
-
Q) Req u i res 4000A construction
Table 46.2
Estimated 400 Hz Interrupting Ratings
RMS Symmetrical Amperes - Not UL Listed
Standard Break
Frame Size
Max. Rating Plug
(Amps)
Ampacity@
800
600
1600
1000
2000
1200
2500
1600
Hi-Break
(Amps)
Am pocity@
Frame Size
Max. Rating Plug
800
600
1000
1600
1200
2000
1600
2500
@ No additional thermal derating is required for above-maximum rating
plug ratings far frame sizes noted. Note: 400Hz interrupting ratings ore
based on engineering judgment, taking into consideration the operating
cha racteristics of insulated case circuit breakers and the worldwide lack
of test facilities to verify performance. Power+™ trip units and the energy
ma nagement functions in MicroVersaTrip PM™ trip u nits are suitable for
50/60 Hz a p plications only.
Frame Size
1600 -
2500 -
2000A
3000
4000A
85
100
100
65
100
100
50
85
85
1 2 5
200
200
100
150
150
65
100
100
40
42
42
7 5 Q)
7 5
85
45 Q)
25
56
50 Q)
40
50
120/240
277/480
346/600
6500
5000
4200
8500
6500
5000
8500
6500
5000
10000
10000
8500
277/480
346/600
120/140
10000
10000
6500
1 2 500
10000
6500
1 2 500
10000
6500
20000
15000
10000