Catalog N u mbers
This section contains the nomenclature system for Power Break® I I circuit breakers, Power+™, MicroVersaTrip Pl us™ and
MicroVersaTrip PM™ trip units and the interchangeable rating plugs.
Power B reak® I I Circuit Breaker Catalog N u m bers
Power Break II breaker type
Current interrupting capacity
S = Sta ndard break
®
H = H i Breok
breaker
Construction
D = Drowout
F = Stationary, front connected
B = Bock con nected, 2500-3000A o n ly
Frame rating
08 = SOOA
25 = 2500A
16 = 1600A
30 = 3000A
20 = 2000A
40 = 4000A
Accessory Cata log N u m bers
Power Break II breaker
AS = Auxiliary switch*
BAA = Bell alarm, alarm o n ly*
BAL
Bell alarm with lockout*
=
COUNTER = Mechanical counter*
O I L = Defeoto ble door i nterlock
DOSD = Drawout secondary disconnects
DOWB = Drawout mecha n ical interlock
DSS = S u bstructure shutter kit*
E = Electric operator*
H DOS = H i- B reak rated drawout sustructure*
K4 = Kirk Key lock (4 maxi m u m)*
PBCOVER = Pushbutton cover*
RCS = Remote close solenoid*
S DOS = Sta ndard rated drowout substructure*
ST = Shunt trip*
STL = Shunt tri p with lockout
UV
U ndervoltoge release*
=
WB = Wa l king beam for stationary breakers
08 = SOOA T -stud
520 = 2000A T -stud (3 000A fra me)
20 = 1600 thru 2000A T-stud
52 5 = 2 500A T -stud
S30 = 3000A T -stud
S40 = 4000A T -stud
RAILS = Roil kit
LUGA = Lug adopter kit
B = Enclosure
* Device Cot. No. req u i res on extender " R" for field insto l loble kit version o n ly.
S
S
D
08
*
02
H
T ·r
SP
AS
240
AB4D
R
Auxiliary function
= H igh-ra nge instanta neous c u rrent sonsors
o n k = Sta ndard c u rrent sensors
rrent sensor rating
02 = 200A
20 = 2000A
04 = 400A
25 = 2 500A
08 = SOOA
30 = 3000A
10 = 1000A
40 = 4000A
16 = 1600A
Trip u n it type and rating
B = E n hanced MicroVersoTrip Plus and
M icroVersoTrip PM trip un it;
D = Power+ trip u n it
B2/D2 = 2000A maximum
B3/D3 = 2500, 3000A
B4/D4 = 4000A
Extender
R = Field insto l loble kit
Bla n k = Factory i n stal led
Auxiliary switch extender
AB4 = Auxiliary switch, type AB with 4 ele ments
ABS = Auxiliary switch. type AB with 8 elements
A B 1 2 = Auxiliary switch, tdype AB with 12 elements
(Add suffix "D" for Drawout construction
Voltage, unless otherwise stated
0 1 2 = 12 Vdc
024
24 Vdc
=
048
48 Vdc
=
1 20/1 2 5
120 Voc or 125 Voc
=
240/250 = 240 Voc and 250 Voc
2 5 0 = 250 Vdc
480 = 480 Voc
600 = 600 Voc
08 = SODA
25 = 2 500A
16 = 1600A
30
3000A
=
20 = 2000A
40
4000A
=
BCA = Bock connected aluminum
BCC = Bock connected copper
FCA = Front connected aluminum term i na l T-stud
LFCC = Front conn ected copper. long stud
3 6 B = 3 6 secondary disconnects, breaker
36C = 3 6 secondary descon nects, su bstructure
CD
Hig h-range instantaneous sensors only available on
MicroVersaTrip Plus and MicroVersoTrip PM units. For
availabi lity of Power+ Tip Untis, contact your ED&C soles
engineer.