Application
V. I ndividual Pole Short-Circuit Test Seq uence (lsu)
1 .
I n d ividual Pole Short-Circuit Brea king Capacity:
Power Break® I I Circuit breakers a re tested to com plete a
series of short-circuit interruptions with a 3-minute rest
period between interruptions. The breakers must com
plete an "open" operation followed by a "close-open"
operation on each pole individually. The circuit breakers
a re tested with an open circuit voltage sufficient to en
able a recovery voltage of the rated voltage plus 5%. The
800-2000 a m p Power Break I I circuit breakers a re tested
using two phases of a three-phase 2 5,000 a m p rms
symmetrical, 50 Hz, 25% power factor short circuit.
2.
Verification of Dielectric Withstand:
Following the short-circuit interruptions, the breakers
main circuit is verified to withstand a voltage equal to
twice its rated insulation voltage; however, not less than
1000 V for 1 min ute.
3.
Verification of Overload Release:
Following the dielectric verification, the circuit breaker
overload p rotection is verified by a pplying 2 50% of rated
current through each pole individually. The breaker must
trip withi n the trip time cu rve.
Table 42.1
Test Tolerance: Unless Otherwise Specified
All Tests
Load or Over Load
Cu rrent
+5%-0%
+5%-0%
Voltage
Frequency
-
Power Foetor
-
Power B reak®
I I -
100 ° / o Rated Circuit Breakers
Power Breaker I I circuit breakers a re U L Listed to ca rry 100%
of rating-plug nameplate current , continuously ® , when
insta lled in accordance with guideline pri nted on the brea ker,
and as detailed in the following Cu rrent Rating Factors por
tion of this section.
Standard Rated Devices
A "Sta ndard rated" device is rated to carry 100% of its name
plate cu rrent for short periods of time (up to 3 hours maxi
mum) when enclosed in equipment , such a s a switchboard.
The enclosed device has a conti nuous rating of 80% of rating
according to current versions of the N atio nal Electric Code
(Article 2 20- 10).
100% Rated Devices
100% rated devices a re designed to ca rry 100% of their
nam eplate cu rrent rating when enclosed and tested in distri
b ution equipment.
(})
4000
80 %
A stationary
42
No Load, Normal
Short Circuit
3500
-
2500
-
±5%(47.5-52 5 Hz)
±5%(475-52 5 Hz)
±0.05
+0 -0.05
Breakers with 100% rating a re so m arked on the front of
the devices. This marking includes minimum enclosure size,
minimum venti lation (if a ny) , minimum cable sizes and tem
perature rati ngs to be used. Current versions of the National
Electric Code permit such use i n the exceptions to Articles
2 10-2 2(c) and 2 20-10 (b).
Factors Affecting the Current Ratings
of I nstalled Devices
There a re six application factors to consider in selecting cur
rent rati ng on instal l ed Power Break
b reakers. These a re: 1) the size of the cable or bus used in
the line and load connections, 2) the actua l i nstalled am bient
temperature, 3) the system operating frequency, 4) the a lti
tude of the insta llation, 5) the type of loading of the protected
circuit, and 6) the design safety factor.
The fol lowing simple relationship combines these six a ppl ica
tion factors into a single equation:
I CB
c
=
X A X B X
X D X E X F
l
A
= I nsta lled circuit brea ker cu rrent rati ng, a m ps
l
cs
= Actual load current , amps
l A
A = Cable of bus sizing factor
B = Am bient temperature rating factor
C = Frequency rating factor
D = Altitude rating factor
E = Load class rating factor
F = Safety factor
Ca ble or Bus Size
The thermal design of a circuit breaker takes i nto account
the abil ity of the line and load cables o r buses to act as heat
si nks. Sta ndard U L 489 has assigned specific cable or bus
sizes for each curre nt rating. General ly, these assig nments
a re coordinated with specific conductor temperature ratings.
I ncreasing a conductor's temperature rating decreases both
the cross-sectional a rea and its ability to cond uct heat from
the circuit b reaker. The chart below ill ustrates the effect of
changing cable a reas on the cu rrent-ca rrying ability of the
circuit breaker.
% Change in current ca rrying ability
+50%
Current rating
+ 25
% of change
�
·25%
-50%
Rated
conductor
Effects of changing load a n d l i n e conductor sizes
I I
insu lated case circuit
200% of rated
conductor size
Need help?
Do you have a question about the Power Break II and is the answer not in the manual?
Questions and answers