Accessories

Shunt Trip With Lockout

The shunt trip with lockout is similar to the regular shunt trip.
When energized. the sh unt trip with lockout module sends a
signal to the trip u nit to open the breaker. I n addition. when
continuously energized with the breaker open. a plunger in
the module acts upon the mechanism. blocking manual and
electric closing by preventing mechanism spring discharge.
To close the breaker, de-energize the module for 250 ms. Be­
cause the b reaker mova ble contacts o re restra ined and can­
not momentarily touch the stationary contacts. the mecha­
nism remains "kiss-free". This feature is especially i m portant
in main-tie-main schemes or generator circuits.
Table 27. 1
Shunt Trip Module with Lockout
Catalog
Voltage
Maximum
N u m ber
Rating
Operating
Voltage
(50-60 Hz)
(Volts)
SPSTL012
12 Vdc
SPSTL024
24 Vac/dc
SPSTL048
48Vac/dc
SPSTL120
120Vac/125
Vdc
SPSTL208
208Vac
228
SPSTL240
240 Vac/250
264
Vdc
SPSTL480
480 Vac
528
SPSTL600
600Vac
660
Peak I n rush
Nominal Input
Cu rrent
Current
lAC Am ps)
lAC RMS mA)
14
19
300
2 6
1 5
300
53
7 . 5
200
1 3 2
3
80
1.9
60
1. 5
45
3
6 5
3
65
Bell Alarm (Ala rm Only)
The bell alarm module is used to signal breaker "tripped" sta­
tus to other a ccessories (e.g. externa l alarm devices. indicat­
ing lig hts. relays, or logic circuits) for remote ind ication a n d
interlocking functions. T h e switch is config urable b y means
of rear-mounted DIP switches on the M icroVersaTrip Pl us™
and PM™ trip u nits. The bell a l a rm can be made to oper-
ate in response to an overcurrent ( including g round fau lt) or
p rotective relay trip and/or a shunt trip operation. and/or
operation of the undervoltage release module. It is not actu­
ated as a result of normal breaker "ON/OFF' operation. For
the Power+™ trip unit, the bell alarm operates only when an
overcurrent (including g round fault) trip occurs.
This module p rovides a visual. mechanical pop-out target
wh ich protrudes through the face of the circuit breaker door
when it operates. The bell alarm may be reset manually by
depressing the mechanica l target, or automatical ly by clos­
ing the b reaker.
The bell alarm is p rovided with one SPOT switch with control
power duty contacts as shown in Table 27.2.

Bell alarm

Table 27.2
Ratings
Bell Alarm Module
Catalog Number
AC
SPBAA240
6 A @ 240 Vac
S P BAA600 CD
6A @ 600 Vac
CD 600 Vac module not UL listed
Ratings
DC
0.5 A @ 125 Vdc
0.25 A @ 250 Vdc
0.5 A @ 125 Vdc
0.25 A @ 250 Vdc