Power+™ Trip Units
Long-Time Protective Functions
I
Long-Time Function
Current Setting (Standard)
The adjustable long-time setting is based on multiples of "X",
the rating plug a m p rating. There are 7 possible settings from
50% to 100% of rating plug a m ps. This setting establishes
the current setting of the breaker, which is the current the
breaker will carry continuously without trippi n g. M u ltiplying
the long-time setting by the rating plug va lue establishes the
value of "C". For exa mple, a breaker with a 95% long-time
setting and 500-amp rating plug (X), would have a 475-amp
current setting, or value of C.
( Long-time current setting (C)= (0.50 to 1.00) x rating plug (X))
7
.8
Long-time function or c u rrent setting
Long-Time Delay (Standard)
Long-time delay varies the time it wil l take the brea ker to tri p
under sustained overload conditions. I t permits the breaker
to ride thro ugh momentary pred icta ble overloads (e.g., mo
tor starting) without tri pping. There are 4 time bands that
provide nominal delays from 3 to 25 seconds at 600% of the
setting, or value of C.
breaker's current
Long-time delay
10
I n sta ntaneous Function (with Power+ Trip U n its)
All Power Break® II breakers have the standard instanta
neous tri p function. The instantaneous tri p point esta blishes
the value of current that will tri p the brea ker without inten
tional time delay. Instantaneous tri p times are 50 millisec
onds, or less. Instantaneous trips are the result of severe
overcurrent or short-circuit conditions. and damage to the
power system is m inimized by immediate tripping. Stand ard
setting s are a djusta ble in multiples of the rating plug amp
value (X). See Ta ble 11.1 for a l lowa ble values. The trip unit will
limit the instantaneous tri p level so that the breaker with
stand r ating is not exceeded. Maximum setting is dependent
on breaker frame size.
1.5
1 0 I 9
Standard instantaneous function
Short-Time Functions (Optional)
Short-Time Pickup
The short-time pickup function controls the level of high cur
rent the breaker will withstand for short periods of time to
al low downstream devices to clear fau lts without tri pping the
breaker. Settings are a dj ustable in increments of the breaker
(C).
nt
curre
settin g
See Table 11.1
instantaneous setting is set for lower values of current than
the short-time function. the instantaneous function prevails.
, - 1 - . 5
I
2. 5
I
S h o rt-time pickup function
for allowable val ues.
the
If