MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Otherwise, a Warning is displayed in the compilation phase and in the report.
The user must adopt additional safety measures during the Override phase.
"With sensors
occupied " selected
X
-
Timeout (sec): Used to set the time, between 10 sec and infinity, by which the Override
function must end.
Override mode: Used to configure the type of Override (pulsed or maintained action).
With OverOut: Used to activate an Override active Signaling output (active when high).
With Request: Used to activate a Signaling output (active when high) indicating that the
Override function can be activated.
Manual Reset:
Should the INPUT be active (TRUE), the reset enables the output of the function
block.
Should the INPUT be not active (FALSE), the output of the function block follows the
OVERRIDE request.
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double
transition from 0 to 1 and then back to 0 is verified.
8540780 • 23/03/2017 • Rev.31
Conditions to be checked for activation of Override
sensor
curtain
occupied
occupied
X
-
X
X
light
Override
Input
request
-
0
X
0
-
0
X
0
Override
output
1
1
1
1
1
1
1
1