Reer Mosaic MI8 Installation And Use Manual page 128

Modular safety controller
Hide thumbs Also See for Mosaic MI8:
Table of Contents

Advertisement

Figure 62
shows the traces relative to the operation. These are described in detail below:
(1)
(2) At this time the electromagnet is activated with a delay of "Unlock Time", after the
command is sen
switches from LL0 to LL1.
(3) At this time the electromagnet is actually activated, 95ms after the command was
sent. This delay is due to the technical characteristics of the electromagnet. In any
case, 95ms is less than100ms ("Feedback Time") and so no errors have occurred.
(4) At this time the guard lock is unlocked and the user opens the gate, the FBK_GATE
signal switches from LL1 to LL0.
(5) At this time the user closes the gate and the FBK_GATE signal thus switches from
LL0 to LL1.
(6)
the gate closed condition, via the FBK_GATE signal, and sends a command to lock
(7) At this time the electromagnet is actually deactivated, approx. 95ms after the
command was sent due to the technical characteristics of the device. The guard
lock is now locked.
(8)
Figure 62 - Traces relative to "Guard Lock" block operation in the with gate mode.
128
OUTPUT1
OUTPUT1
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
8540780 • 23/03/2017 • Rev.31