MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
3) The counter generates a pulse duration equal to the system response time as soon as the
set count is reached. If the CLEAR signal is activated, the internal count goes back to 0.
Parameters
Clear Enable: If selected this enables the request to clear in order to restart the counter
setting output Q to 0 (FALSE). It also offers the possibility of enabling or not enabling
(Automatic Enable) automatic operation with manual reset.
If this is not selected operation is automatic. Once the set count is reached output Q is
set to 1(TRUE) and stays in this condition for 2 x Tcycle (indicated in the REPORT) after
which it is resetted.
Ck down: Enables counting down.
Two-way: If selected it enables counting on both the rising and falling edges.
8540780 • 23/03/2017 • Rev.31