Figure 65 – Example of possible error condition in "Mandatory gate opening" mode. In this case the
error condition is generated because the gate has not been opened, even though a request has
been sent to unlock/lock the guard lock.
Parameters
Manual Reset:
There are two types of reset: Manual and Monitored. When Manual is selected the system
only verifies the signal's transition from 0 to 1. If Monitored is selected the double
transition from 0 to 1 and then back to 0 is verified.
Important: for Manual reset always use the input immediately after those used by the
function block. E.g.: if inputs 1 and 2 are used for the function block, use input 3 for
Reset.
132
t = 250 ms
MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
t1 > 250 ms
t2 = 250 ms
8540780 • 23/03/2017 • Rev.31