MODULAR SAFETY INTEGRATED CONTROLLER MOSAIC
Unlock Time (s):
The time that must pass between the UnLock_cmd input reaching and the real guard unlock
(Lockout output).
-
0ms ÷ 1 s Step 100 ms
-
1.5 s ÷ 10 s Step 0.5 s
-
15 s ÷ 25 s Step 5 s
Feedback Time (s):
Maximum delay accepted between LockOut output and Lock_fbk input (must be the one shown
on the lock data sheet with appropriate gap decided by the operator).
-
10ms ÷ 100 s Step 10 ms
-
150ms ÷ 1 s Step 50 ms
-
1.5 s ÷ 3 s Step 0.5 s
Mandatory gate opening: Only with door opening and subsequent confirmation of input GATE,
the cycle proceeds.
Gate not present: If selected, enables configuration without Gate but only with LOCK FEEDBACK
(feedback coil lock).
Interlock Spring: The guard is locked passively and released actively, i.e. the mechanical force of
the spring keeps it locked. The guard thus continues to be locked even when the power supply is
disconnected.
Enable error out: This can be selected to enable a signal (Error Out) to indicate a lock
malfunction. When Error Out = 1 (TRUE) there is a fault in the lock.
8540780 • 23/03/2017 • Rev.31