Error messages via the
indicating and adjust-
ment module
VEGADIF 65 • Foundation Fieldbus
Error
Cause
When an additio-
Max. supply cur-
nal instrument is
rent of the seg-
connected, the H1
ment coupler
segment fails.
exceeded
Measured value
The menu item
Display - Dis-
on the indicating
"
and adjustment
play value
module does not
not set to "
correspond to the
Out
value in the PLC
Instrument does
Profibus DP cab-
not appear during
le pole-reversed
connection setup
Incorrect termina-
tion
Instrument not
connected to the
segment
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
?
E013
no measured value available
l
à Exchange the instrument or send it in for repair
?
E017
Adjustment span too small
l
à repeat with modified values
?
E036
no operable sensor software
l
à Carry out a software update or send instrument for repair
?
E041
Hardware error
l
à Exchange the instrument or send it in for repair
7)
Fault message can also appear if the pressure is higher than the nominal
range.
9 Maintenance and fault rectification
Removal
Measure the current consumption,
reduce size of segment
Check values and correct, if neces-
sary
" is
AI-
"
Check cable and correct, if necessary
Check termination at the beginning
and end points of the bus and termin-
ate, if necessary, according to the
specification
Check and correct, if necessary
7)