4.6 Measurement setup density and interface

In a vessel with varying level and homogeneous density distribution,
density measurement with a differential pressure transmitter can be
realized. The connection to the vessel is made via a chemical seal on
two measuring points. To reach a high accuracy, the distance between
these points must be as big as possible. The density measurement is
only ensured with a level above the upper measuring point. If the level
drops below the upper measuring point, the density measurement is
interrupted.
This density measurement functions with open but also with closed
vessels. Make sure that small density changes cause only small
changes to the measured differential pressure. Select a suitable
measuring range.
The density measurement is carried out in the mode level measure-
ment.
à Mount VEGADIF 65 below the lower chemical seal
à The ambient temperature should be the same for both capillaries
Example for a density measurement:
Distance between the two measurement points: 0.3 m
Min. density: 1.0 kg/dm
Max. density: 1.2 kg/dm
Measured differential pressure: Δp =
+
5
3
3
• g • h
VEGADIF 65 • Foundation Fieldbus
1
2
3
4