Differential pressure transmitter with
metallic measuring cell
VEGADIF 85
Profibus PA
Document ID: 53575

Advertisement

Table of Contents
loading

Summary of Contents for Vega VEGADIF 85

  • Page 1 Quick setup guide Differential pressure transmitter with metallic measuring cell VEGADIF 85 Profibus PA Document ID: 53575...
  • Page 2: Table Of Contents

    Operating Instructions Manual as well as the Safety Manual that comes with instruments with SIL qualification. These manuals are available on our homepage. Operating instructions VEGADIF 85 - Profibus PA: Document-ID 53569 Editing status of the quick setup guide: 2023-08-04...
  • Page 3: For Your Safety

    During work on and with the device, the required personal protective equipment must always be worn. Appropriate use VEGADIF 85 is an instrument for measurement of flow, level, differen- tial pressure, density and interface. You can find detailed information about the area of application in chapter "...
  • Page 4: Namur Recommendations

    The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter " Packaging, transport and storage" • Chapter " Disposal" VEGADIF 85 • Profibus PA...
  • Page 5: Product Description

    To find order data, documents or software related to your device, you have the following options: • Move to " www.vega.com" and enter in the search field the serial number of your instrument. • Scan the QR code on the type label.
  • Page 6: Mounting

    To maintain the housing protection, make sure that the housing lid is closed during operation and locked, if necessary. Ventilation The ventilation for the electronics housing is realised via a filter ele- ment in the vicinity of the cable glands. VEGADIF 85 • Profibus PA...
  • Page 7 Plastic double chamber Aluminium, stainless steel double chamber housing (precision casting) Filter element Information: Make sure that the filter element is always free of buildup during op- eration. A high-pressure cleaner may not be used for cleaning. VEGADIF 85 • Profibus PA...
  • Page 8: Connecting To Power Supply

    7. Check the hold of the wires in the terminals by lightly pulling on them 8. Connect the shielding to the internal ground terminal, connect the external ground terminal to potential equalisation VEGADIF 85 • Profibus PA...
  • Page 9: Single Chamber Housing

    6 7 8 Fig. 4: Connection compartment - double chamber housing Voltage supply, signal output For display and adjustment module or interface adapter For external display and adjustment unit Ground terminal for connection of the cable screening VEGADIF 85 • Profibus PA...
  • Page 10: Set Up With The Display And Adjustment Module

    The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 5: Installing the display and adjustment module in the electronics compart- ment of the single chamber housing VEGADIF 85 • Profibus PA...
  • Page 11: Parameter Adjustment - Quick Setup

    126. This means that the address can be changed via the display and adjustment module. Measurement loop name In this menu item you assign a suitable measurement loop name. Permitted are names with a maximum of 19 characters. VEGADIF 85 • Profibus PA...
  • Page 12 In this menu item you carry out the max. adjustment for flow. Enter the percentage value and the corresponding pressure value for the max. flow. Linearisation In this menu item, you select the characteristics of the output signal. VEGADIF 85 • Profibus PA...
  • Page 13 Enter the percentage value and the corresponding height of the interface. Max. adjustment In this menu item, you carry out the adjustment for the max. height of the interface. Enter the percentage value and the corresponding height of the interface. VEGADIF 85 • Profibus PA...
  • Page 14 (SV, TV) must be carried out via PACTware. The quick setup is finished. Parameterization example VEGADIF 85 always measures pressure independently of the process variable selected in the menu item " Application". To output the se- lected process variable correctly, an allocation of the output signal to 0 % and 100 % must be carried out (adjustment).
  • Page 15: Parameter Adjustment - Extended Adjustment

    Default value Instrument ad- dress Measurement Sensor loop name Application Application Level Units Unit of measure- mbar (with nominal measuring range ment ≤ 400 mbar) bar (with nominal measuring ranges ≥ 1 bar) Temperature unit °C VEGADIF 85 • Profibus PA...
  • Page 16 Date/Time Actual date/Actual time Copy instru- No reset ment settings Special pa- No reset rameters Scaling Scaling size Volume in l Scaling format 0 % corresponds to 0 l 100 % corresponds to 0 l VEGADIF 85 • Profibus PA...
  • Page 17 Info Menu item Parameter Device name Device name Instrument version Hardware and software version Factory calibration date Date Profibus Ident Number Identification number of the instrument on a Profi- bus system Sensor characteristics Order-specific characteristics VEGADIF 85 • Profibus PA...
  • Page 18: Set Up With Smartphone/Tablet, Pc/Notebook Via Bluetooth

    PIN in the adjustment menu of the sensor, e.g. to " 1111": 1. Go to setup via the extended operation 2. Lock operation by changing sensor PIN 3. Enable operation by entering the sensor PIN once more VEGADIF 85 • Profibus PA...
  • Page 19: Connecting

    Bluetooth-capable instru- ments in the area. PC/Notebook Start PACTware and the VEGA project assistant. Select the device search via Bluetooth and start the search function. The device auto- matically searches for Bluetooth-capable devices in the vicinity.
  • Page 20 6 Set up with smartphone/tablet, PC/notebook via Bluetooth App view Fig. 9: Example of an app view - Setup sensor adjustment VEGADIF 85 • Profibus PA...
  • Page 21: Supplement

    Operating voltage U 9 … 32 V DC Operating voltage U with lighting 13.5 … 32 V DC switched on Number of sensors per DP/PA segment coupler, max. IP66/IP68 (0.2 bar), only with absolute pressure. VEGADIF 85 • Profibus PA...
  • Page 22 Notes VEGADIF 85 • Profibus PA...
  • Page 23 Notes VEGADIF 85 • Profibus PA...
  • Page 24 Subject to change without prior notice © VEGA Grieshaber KG, Schiltach/Germany 2023 VEGA Grieshaber KG Am Hohenstein 113 Phone +49 7836 50-0 77761 Schiltach E-mail: info.de@vega.com...