Vega VEGADIF 65 Operating Instructions Manual page 50

Foundation fieldbus, differential pressure transmitter
Table of Contents

Advertisement

6 Adjustment with the indicating and adjustment module PLICSCOM
Zero adjustment with
differential pressure
Span adjustment with
differential pressure
50
The current measured value was corrected to 0, the corrective value is
available in the display as offset value with sign reversal.
If a known value should be taken over as position correction which is
not the current value, then you have to select the function "Edit" and
enter the requested value.
In this menu item, the min. differential pressure is entered.
Proceed as follows:
1
Edit the bar value in the menu item "zero" with [OK].
Zero adjustment
0.00 %
DP
=
0.0000 bar
0.0000 bar
2
Set the requested value with [+] and [->].
3
Confirm with [OK] and move to span adjustment with [->].
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
The zero adjustment is finished.
Information:
The zero adjustment shifts the value of the span adjustment. The span,
i.e. the difference between these values, however, remains un-
changed.
In this menu item, the max. differential pressure is entered.
Proceed as follows:
1
Edit the bar value in the menu item "span" with [OK].
Span adjustment
100.00 %
DP
=
0.5000 bar
0.0000 bar
Information:
When the instrument is not yet adjusted, then the display pressure for
100 % corresponds to the nominal measuring range of the sensor (in
the above example 500 mbar).
2
Set the requested value with [+] and [->].
3
Confirm with [OK] and move to the menu overview with [ESC].
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
VEGADIF 65 • Foundation Fieldbus

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents